OSG Reference: Section 2.2.2
A.21 Ohms
B.3. For a standard TT supply up to 100 A, what is the maximum expected value of external earth loop impedance ( Z e ) typically quoted by DNOs?
C.0.8 Ohms
D.0.35 Ohms
OSG Reference: Section 2.4.2
A.A metal switch plate on a plastic box
B.6. Which of the following is considered an extraneous-conductive-part requiring main protective bonding?
C.An un-insulated metallic structural steel framework
D.A plastic water main
A steel wire armored cable tray
A.OSG Reference: Section 2.4.1
B.Correct Answer: An un-insulated metallic structural steel framework
C.7. Where must a main protective bonding connection be ideally made to a metallic gas service pipe entering a building?
D.Within 2 meters of the appliance
On the consumer's side of the meter, within 600 mm of the meter outlet
A.OSG Reference: Section 2.4.4 / Figure 2.4
B.On the supplier's side of the meter before the emergency control valve
C.Correct Answer: On the consumer's side of the meter, within 600 mm of the meter outlet
D.Anywhere along the pipework inside the kitchen
8. What is the minimum size of a supplementary bonding conductor connecting two exposed-conductive-parts if it is NOT mechanically protected?
A.2.5mm^2
B.4.0mm^2
C.1.5mm^2
D.6.0mm^2
If the floor is covered with non-conductive vinyl tiles
A.If the lighting circuit uses plastic fittings only
B.Correct Answer: If all circuits are protected by a 30 mA RCD, disconnection times are met, and extraneous parts are effectively bonded
C.OSG Reference: Section 2.5.2
D.10. What type of test instrument is used to verify the effectiveness of a main protective bonding connection?
Insulation Resistance Tester
A.Prospect Fault Current Tester
B.Low-resistance Ohm meter (Continuity Tester)
C.Correct Answer: Low-resistance Ohm meter (Continuity Tester)
D.Earth Loop Impedance Tester
OSG Reference: Section 2.4 / Section 6
A.0.2 seconds
B.Subsection 2: Circuit Protection & Disconnection Times (OSG Section 3 & Appendix
C.11. What is the maximum permitted disconnection time for a final circuit not exceeding 32 A supplying a socket-outlet in a 230V TN system?
D.0.4 seconds
Correct Answer: 1.0 second
A.BS 3036
B.BS EN 60898 (MC
C.13. Which type of circuit breaker operates on both a thermal bimetallic strip for overloads and an electromagnetic coil for short circuits?
D.BS 88-2
Between 5 and 10 times I n
A.Exactly 1 time I n
B.Between 10 and 20 times I n
C.OSG Reference: Section 3.1.1 / Appendix B
D.Correct Answer: Between 3 and 5 times I n
15. What is the maximum permitted Z s value for a 32 A Type B BS EN 60898 MCB to ensure a 0.4-second disconnection time in a 230V system (corrected for operating temperature)?
A.2.19 Ohms
B.0.57 Ohms
C.1.10 Ohms
D.1.37 Ohms
Correct Answer: 1.10 Ohms (Note: This is the 80% rule/corrected value tabulated in the OSG)
A.16. For a 40 A Type C BS EN 60898 MCB, what is the maximum tabulated Z s value allowed for a 0.4-second disconnection time?
B.1.10 Ohms
C.0.44 Ohms
D.OSG Reference: Table B6
18. What does an RCD with a rated residual operating current ( \Delta I n ) of 30 mA provide when used in a circuit?
A.Overload protection only
B.Fault protection only
C.Additional protection
D.Isolation only
Correct Answer: Additional protection
A.19. Which device is specifically designed to detect and disconnect circuits experiencing dangerous micro-arcs caused by loose terminal connections or damaged insulation?
B.AFDD
C.OSG Reference: Section 3.3.1
D.RCD
Sustained overvoltage from the grid
A.Correct Answer: Transient overvoltages caused by lightning or switching events
B.Transient overvoltages caused by lightning or switching events
C.Overload currents
D.Earth faults
OSG Reference: Section 3.5
A.3% (6.9 V)
B.Subsection 3: Cable Selection & Voltage Drop (OSG Section 4 & Appendix F)
C.21. What is the standard maximum permitted voltage drop for a low-voltage lighting circuit supplied directly from a public distribution system?
D.4% (9.2 V)
OSG Reference: Table 4.2 / Section 4.3.2
A.0.87
B.25. What rating factor ( C a ) must be applied to a cable if the ambient temperature of the room it passes through is 45^\circ\text{C and it has 70^\circ\text{C thermoplastic insulation?
C.0.71
D.1
27. What is the tabulated current-carrying capacity ( I t ) of a 2.5mm^2 thermoplastic twin and earth cable installed using Method C (clipped direct)?
OSG Reference: Section 4.3
A.30. Which formula is used to calculate the actual minimum required current-carrying capacity ( I z ) of a cable when rating factors apply?
B.I z = \frac{I b{R {e
C.I z = \frac{I n{C a \times C g \times C i \times C f
D.I z = I b \times C a \times C g
32. What visual warning identifier must be placed directly above an underground cable run?
A.Red hazard tape
B.Concrete paving flags only
C.A yellow plastic warning tile or tape marked "Electric Cable Below"
D.A wooden stake painted red
Correct Answer: A yellow plastic warning tile or tape marked "Electric Cable Below"
A.150 mm
B.100 mm
C.50 mm
D.33. When routing cables vertically or horizontally within walls, what is the width of the recognized "safe zone" running directly from an accessory plate or switch?
Equal to the width of the accessory plate or fitting
A.Correct Answer: Equal to the width of the accessory plate or fitting
B.OSG Reference: Section 5.2.2 / Figure 5.1
C.Hand-drawn only
D.34. If a cable is installed outside a recognized safe zone in a wall partition at a depth of less than 50 mm, it must be:
Covered in heavy PVC wrap
A.Provided with mechanical protection capable of resisting nails/screws OR have 30 mA RCD protection
B.Correct Answer: Provided with mechanical protection capable of resisting nails/screws OR have 30 mA RCD protection
C.OSG Reference: Section 5.2.2
D.Painted bright red
35. To prevent structural weakness, a hole drilled through a timber floor joist must be located within what zone of the joist's overall length?
A.Within 100 mm of the supporting wall only
B.Between 0.25 and 0.4 times the span length from either support end
C.Anywhere along the joist
D.Exactly in the middle of the room
Correct Answer: Between 0.25 and 0.4 times the span length from either support end
A.36. What is the maximum permitted diameter of a hole drilled through a structural timber floor joist?
B.0.5 times the depth of the joist
C.OSG Reference: Section 5.1.2 / Figure 5.2
D.0.25 times the depth of the joist
6 times the overall diameter
A.Correct Answer: 4 times the overall diameter
B.10 times the overall diameter
C.OSG Reference: Table 4.5
D.38. When installing containment systems, what is the maximum recommended support spacing interval for vertically mounted rigid PVC conduit?
An internal fire barrier or intumescent fire-stop seal
A.An un-insulated copper bond
B.A change to steel conduit
C.OSG Reference: Section 5.1.1
D.Correct Answer: An internal fire barrier or intumescent fire-stop seal
Subsection 5: Inspection, Testing, and Special Locations (OSG Section 6 & 7)
A.41. What is the sequence order for the first three dead tests during an initial verification sequence?
B.Continuity of protective conductors, Continuity of ring final circuit conductors, Insulation resistance
C.Earth loop impedance, Polarity, RCD operation
D.Insulation resistance, Continuity of protective conductors, Polarity
Voltage drop, Polarity, Continuity
A.OSG Reference: Section 6.1
B.42. What is the minimum acceptable insulation resistance value for a new 230 V final circuit tested at 500 V DC?
C.Correct Answer: Continuity of protective conductors, Continuity of ring final circuit conductors, Insulation resistance
D.0.5M\Omega
43. Which special location zone incorporates the interior of a bathtub basin or a shower tray?
A.Zone 1
B.Zone 2
C.Zone 0
D.Zone 3
OSG Reference: Section 7.2.3
A.46. What type of extra-low voltage supply is explicitly required for an item to be safely installed within Zone 0 of a swimming pool?
B.SELV not exceeding 12V AC or 30V DC
C.PELV at 50 V
D.FELV at 110 V
Standard 230 V with an RCD
A.30 mA
B.Correct Answer: SELV not exceeding 12V AC or 30V DC
C.47. In agricultural and horticultural locations (farms), what is the maximum operating current of an RCD providing fire protection against fault currents?
D.OSG Reference: Section 7.3
48. When testing a 30 mA RCD providing additional protection, what is the maximum permitted disconnection time when tested at 5 \times \Delta I n ?
A.200 ms
B.40 ms
C.150 ms
D.300 ms
To determine the total power load
A.Electrical Installation Certificate (EI
B.To test the RCD trip speed
C.Correct Answer: To ensure all overcurrent protective devices and switches are installed in the line conductor only
D.50. Which document is specifically used to record information about an alteration or addition to an existing installation that does not involve the creation of a brand-new circuit?
Minor Electrical Installation Works Certificate (MEIW
A.Condition Report (EICR)
B.Schedule of Inspections only
C.Correct Answer: Minor Electrical Installation Works Certificate (MEIW
D.OSG Reference: Section 6.2